PAB - RANGE

From wiki.netio-products.com
Jump to navigation Jump to search

True/False-based evaluation. If the monitored value is in specified interval for a time period defined in timeHysteresis, PAB evaluates to TRUE. Otherwise it evaluates to FALSE.

Description

  • Source
  • Parameters
  • Outputs

Structure

Variable Value Description
type RANGE PAB type
source OUTPUTS/x/(LOAD/CURRENT/POWER)
INPUTS/x/STATE
The monitored variable. x indicates input / output number.
timeHysteresis int [s] Monitored value must be present in defined interval for amount of time defined here.

Eg: If the time hysteresis is equal to 5, monitored value must be within a defined interval for at least 5s. Only then it will be evaluated.

lowerBound int lower bound of the monitored value
upperBound int upper bound of the monitored value

Examples

Immediate evaluation

The condition evaluates to TRUE immediately as the current value appears between 100 and 200 mA

{
  "type": "RANGE",
  "source": "OUTPUTS/1/CURRENT",
  "lowerBound": 100,
  "upperBound": 200,
  "timeHysteresis": 0
}

Evaluation with delay

The condition evaluates to TRUE when output load is between 200 and 300 Watts for 5s.

{
  "type": "RANGE",
  "source": "OUTPUTS/1/CURRENT",
  "lowerBound": 200,
  "upperBound": 300,
  "timeHysteresis": 5
}