(Schedule definition)
(NR06 - WatchDog for 2 IPs)
Line 183: Line 183:
  
 
== NR06 - WatchDog for 2 IPs ==
 
== NR06 - WatchDog for 2 IPs ==
 +
The WatchDog functionality is used to monitor connectivity to specified IP address (or URL) by sending PING request to it.
  
The WatchDog functionality is used to monitor connectivity to specified IP address (or URL) by sending PING request to it. The ping in this example is sent every 30s and waits 5s for devices to respond.
+
In this example, we monitor two IPs and we want to restart device connected to Output 1 if none of the addresses reply.
If the ping fails 3 times in a row, Watchdog returns <code>false</code> and restarts (ACTION: 2 = SHORT OFF) device connected to first output. After restart, it waits 3 minutes (180 seconds) and starts monitoring again. WatchDog repeats this cycle 5 times and if after 5 restarts still does not receive ping reply, it remains in ERROR state until next successful ping.
+
The ping for both IPs is sent every 30s and waits 5s for device to respond. There are 5 consecutive timeouts tolerated before the ping is considered as failed. When the ping fails, Watchdog returns <code>false</code> and remains in ERROR state.
 +
 
 +
In case both of the defined WatchDogs are in ERORR state, the Rule is triggered which then restarts Output 1.
 +
 
 +
===WatchDogs definition===
 +
 
 +
WatchDog name: '''NR06_WDT_1'''
 +
 
 +
<nowiki>
 +
{
 +
  "target": "192.168.1.51",
 +
  "pingInterval": 30,
 +
  "timeout": 5,
 +
  "maxTimeouts": 5
 +
}</nowiki>
 +
 
 +
WatchDog name: '''NR06_WDT_2'''
 +
 
 +
<nowiki>
 +
{
 +
  "target": "192.168.1.52",
 +
  "pingInterval": 60,
 +
  "timeout": 5,
 +
  "maxTimeouts": 5
 +
}</nowiki>
 +
 
 +
===Rule definition===
 +
 +
Rule name: '''NR06_RULE'''
 +
 
 +
<nowiki>
 +
{
 +
  "conditions": {
 +
    "operator": "AND"
 +
    "WDT/NR06_WDT_1/FAIL": true
 +
    "WDT/NR06_WDT_2/FAIL": true
 +
  },
 +
  "actions": {
 +
    "OUTPUTS/1/ACTION": 2
 +
  }
 +
}</nowiki>
  
 
== NR07 - Synchronized outputs states during working hours ==
 
== NR07 - Synchronized outputs states during working hours ==

Revision as of 11:46, 26 November 2021

NR01 - WatchDog

The WatchDog functionality is used to monitor connectivity to specified IP address (or URL) by sending PING request to it.

The ping in this example is sent every 60s and waits 5s for the device to respond. If the ping fails, Watchdog returns false and restarts (ACTION: 2 = SHORT OFF) device connected to first output. After restart, it waits 120 seconds and starts monitoring again. If the device does not respond, WatchDog remains in ERROR state until next successful ping.

Watchdog definition

WatchDog name: NR01_WDT

{
  "target": "192.168.101.180",
  "pingInterval": 60,
  "timeout": 5,
  "maxTimeouts": 0,
  "timeToReboot": 120
}

Rule definition

Rule name: NR01_RULE

{
  "conditions": {
    "WDT/NR01_WDT/FAIL": true
  },
  "actions": {
    "OUTPUTS/1/ACTION": 2
  }
}

NR02 - Digital Inputs

Rule is used for managing outputs in response to change of Digital Inputs (DI) state. Rule monitors state of first DI. When DI switches from OFF (0) to ON (1), Rule switches (toggles) Outputs 1 & 2 to their opposite states (ACTION 4 = TOGGLE).

Rule definition

Rule name: NR02_RULE

{
  "conditions": {
    "INPUTS/1/STATE": "on"
  },
  "actions": {
    "OUTPUTS/1/ACTION": 4,
    "OUTPUTS/2/ACTION": 4
  }
}

NR03 - Load Watchdog

Rule monitors load (Watts) on Output 1. If the load is between 1-20W for at least 2 minutes, it restarts (ACTION 2 = SHORT OFF) the output. Example uses PAB (Power Analysis Block) functionality to determine if measured value (load in our case) lies in given range for a period of time. When it does, defined Rule triggers device restart.

PAB definition

PAB name: NR03_PAB

{
  "type": "RANGE",
  "source": "OUTPUTS/1/LOAD",
  "lowerBound": 1,
  "upperBound": 20,
  "timeHysteresis": 120
}

Rule definition

Rule name: NR03_RULE

{
  "conditions": {
    "PAB/NR03_PAB/IN": true
  },
  "actions": {
    "OUTPUTS/1/ACTION": 2
  }
}

NR04 - Load Watchdog with alarm to Cloud

Rule monitors load (Watts) on Output 1. If the load is between 1-20W for at least 30 minutes, it restarts (ACTION 2 = SHORT OFF) the output. In addition, it triggers an alarm in NETIO Cloud, which sends a notification to specified email address. This example needs a NETIO Cloud account with Premium version active for first output. There also has to be email notification enabled for the output.

Example uses PAB (Power Analysis Block) functionality to determine if measured value (load in our case) lies in given range for a period of time. When it does, defined Rule triggers device restart and sends alarm to Cloud.

PAB definition

PAB name: NR04_PAB

{
  "type": "RANGE",
  "source": "OUTPUTS/1/LOAD",
  "lowerBound": 1,
  "upperBound": 20,
  "timeHysteresis": 1800
}


Rule definition

Rule name: NR04_RULE

{
  "conditions": {
    "PAB/NR04_PAB/IN": true
  }
  "actions": {
    "OUTPUTS/1/ACTION": 2,
    "CLOUD/OUTPUT/1/ALARM": "${COND_RESULT}"
  }
}

NR05 - Load Watchdog with zones

Rule monitors load (Watts) on Output 1. Measured load is then classified to several zones defined with thresholds (limit values). Depending on the zone in which the measured load is currently located, different actions can be triggered. Load value has to be between defined threshold for at least 10seconds in order to be placed to respective zone. Example is composed of one PAB that classifies the zones and three Rules for 3 separate actions. Actions do the following:

  • Output 1 load lower than 1W: Output 2 = ON
  • Output 1 load between 1-20W: Output 3 = ON
  • Output 1 load between 20-200W: Output 4 = ON

PAB definition

PAB name: NR05_PAB

{
  "type": "ZONES",
  "source": "OUTPUTS/2/CURRENT",
  "thresholds": [
    1,
    20,
    200
  ],
  "timeHysteresis": 10
}

Rules definitions

Rule 1 name: NR05_RULE_1

{
  "conditions": {
    "PAB/NR05_PAB/ZONE": 0
  },
  "actions": {
    "OUTPUTS/2/ACTION": 1,
    "OUTPUTS/3/ACTION": 0,
    "OUTPUTS/4/ACTION": 0,
  }
}

Rule 2 name: NR05_RULE_2

{
  "conditions": {
    "PAB/NR05_PAB/ZONE": 0
  },
  "actions": {
    "OUTPUTS/2/ACTION": 0,
    "OUTPUTS/3/ACTION": 1,
    "OUTPUTS/4/ACTION": 0,
  }
}

Rule 3 name: NR05_RULE_3

{
  "conditions": {
    "PAB/NR05_PAB/ZONE": 0
  },
  "actions": {
    "OUTPUTS/2/ACTION": 0,
    "OUTPUTS/3/ACTION": 0,
    "OUTPUTS/4/ACTION": 1,
  }
}

NR06 - WatchDog for 2 IPs

The WatchDog functionality is used to monitor connectivity to specified IP address (or URL) by sending PING request to it.

In this example, we monitor two IPs and we want to restart device connected to Output 1 if none of the addresses reply. The ping for both IPs is sent every 30s and waits 5s for device to respond. There are 5 consecutive timeouts tolerated before the ping is considered as failed. When the ping fails, Watchdog returns false and remains in ERROR state.

In case both of the defined WatchDogs are in ERORR state, the Rule is triggered which then restarts Output 1.

WatchDogs definition

WatchDog name: NR06_WDT_1

{
  "target": "192.168.1.51",
  "pingInterval": 30,
  "timeout": 5,
  "maxTimeouts": 5
}

WatchDog name: NR06_WDT_2

{
  "target": "192.168.1.52",
  "pingInterval": 60,
  "timeout": 5,
  "maxTimeouts": 5
}

Rule definition

Rule name: NR06_RULE

{
  "conditions": {
    "operator": "AND"
    "WDT/NR06_WDT_1/FAIL": true
    "WDT/NR06_WDT_2/FAIL": true
  },
  "actions": {
    "OUTPUTS/1/ACTION": 2
  }
}

NR07 - Synchronized outputs states during working hours

Rule keeps track of first output state and when it changes, it switches output 2 to the same state. However, we want this synchronization only to work during working hours. We define the time with Schedule functionality and use it as a filter (mask) in Rules. Schedule can be defined manually or imported as a configuration file.

Schedule definition

Schedule name: NR07_SCHEDULE

NR070 Schedule

Rule definition

Rule name: NR07_RULE

{
  "conditions": {
    "OUTPUTS/1/STATE": "on"
  },
  "filters": {
    "SCHEDULE/NR07_SCHEDULE/ACTIVE": true
  },
  "actions": {
    "OUTPUTS/2/ACTION": "${COND_RESULT}"
  }
}