The PAB (Power Analyzing Block) define sets of conditions for measured variables (current, voltage, S0 pulses etc.). Various rules can be set based on these conditions. Rules can perform actions such as sending alarm to the Cloud service, restarting outputs, etc.
+
The PAB (Power Analysis Block) is a function available for NETIO devices that periodically evaluates sets of conditions. Based on these conditions, subsequent [https://wiki.netio-products.com/index.php?title=Rules '''Rules'''] can be executed. These conditions can consist of one or more of following variables:
The PAB condition output is also available for use in selected protocols.
+
* Current [mA]
 +
* Energy [Wh]
 +
* Load [W]
 +
* Power Factor
 +
* S0 pulses
  
There are two types of PAB available:  
+
Rules can then perform several actions described in section [https://wiki.netio-products.com/index.php?title=Rules '''Rules'''].
1) RANGE - Evaluation YES/NO (true/false) 
+
Every PAB is internally evaluated as having a discrete state which can be used as an input to a Rule mentioned above. State value is different for each type of PAB (described below). This state is also available in JSON protocol and therefore can be read externally.
2) ZONE - Evaluation using specified intervals 
 
Each type uses specific variables and is described in detail below.
 
  
PABs can work with the specified quantities:
+
There are two types of PABs available: '''RANGE''' & '''ZONES'''. Each type has different states and configuration options.
  * Current: OUTPUTS/1/CURRENT **[mA]**
 
  * Load: OUTPUTS/8/LOAD **[W]**
 
  * Energy: OUTPUTS/4/POWER **[Wh]**
 
  * Output no. 1 state: OUTPUTS/1/STATE **[int 0/1]**
 
General structure for defining a variable is: `<INPUT/OUTPUT>/ID/<monitored variable>`
 
  
## PAB - RANGE 
 
True/False-based evaluation. If the monitored value is in specified interval for a time period defined in `timeHysteresis`, PAB evaluates as `True`. Otherwise it evaluates as `False`.
 
  
### Structure
+
= RANGE =
 +
True/False-based evaluation. Detects whether a monitored value lies in specified interval (range) for a period of time. PAB evaluates to <code>TRUE</code> or <code>FALSE</code>.
 +
Interval is specified by lower <code>lowerBound</code> and upper <code>upperBound</code> boundaries. PAB evaluates to <code>TRUE</code> if a variable defined in <code>source</code> lies within for a period of time defined in <code>timeHysteresis</code>.
 +
 
 +
== Configuration Structure ==
 
{| class="wikitable"
 
{| class="wikitable"
 
|-
 
|-
Line 29: Line 28:
 
|-
 
|-
 
| source  
 
| source  
| OUTPUTS/**x**/(LOAD/CURRENT/POWER) <br> INPUTS/**x**/STATE
+
| OUTPUTS/'''x'''/(LOAD/CURRENT/POWER)
| The monitored variable. **x** indicates input / output number.
+
| The monitored variable. '''x''' indicates input / output number.
 
|-
 
|-
 
| timeHysteresis  
 
| timeHysteresis  
 
| int  
 
| int  
| [s] Monitored value must be present in defined interval for amount of time defined here. Eg: If the time hysteresis is equal to 5, monitored value must be within a defined interval for at least 5s. Only then it will be evaluated.
+
| [s] Monitored value must be present in defined interval for amount of time defined here.
 +
 
 +
Eg: If the time hysteresis is equal to 5, monitored value must be within a defined interval for at least 5s. Only then it will be evaluated.
 
|-
 
|-
 
| lowerBound  
 
| lowerBound  
Line 45: Line 46:
 
|}
 
|}
  
## PAB - ZONE 
+
== Examples ==
Zone-based evaluation. 1 or more zones can be set. Zones are divided using the values specified in the `thresholds` variable.
 
Monitored value must be present in defined interval for amount of time defined here. The PAB condition is evaluated as a number (integer) equal to the interval order. Eg. At two specified intervals, the PAB value can be 0, 1, or 2.
 
 
 
### Struktura 
 
| Proměnná | Hodnoty | Popis |
 
| ------ | ------ | ------ |
 
| type | ZONE | typ PAB |
 
| source | OUTPUTS/**x**/(LOAD/CURRENT/POWER) <br> INPUTS/**x**/STATE |  Měřená hodnota, kterou sledujeme. **x** udává číslo vstupu/výstupu.|
 
| timeHysteresis | int | [s] Časový interval, ve kterém se musí nacházet sledovaná hodnota. Př.: Pokud je hystereze rovná 5, musí se sledovaná hodnota nacházet v definovaném intervalu (intervalech) alespoň 5s. Až následně dojde k jejímu vyhodnoceí. |
 
| thresholds | list[int] |  seznam spodních hranic intervalů pro přechod mezi zónami
 
  
## Příklady
+
=== Immediate evaluation ===
Podmínka se vyhodnotí jako **true** okamžítě, jakmile se hodnota proudu objeví mezi 100 a 200 mA.
+
PAB evaluates to <code>TRUE</code> immediately as Output 1 '''Current''' value appears '''between 100 and 200 mA'''
```
+
<nowiki>
 
{
 
{
 
   "type": "RANGE",
 
   "type": "RANGE",
Line 66: Line 57:
 
   "upperBound": 200,
 
   "upperBound": 200,
 
   "timeHysteresis": 0
 
   "timeHysteresis": 0
 +
}</nowiki>
  
}
+
=== Evaluation with delay ===
``` 
+
PAB evaluates to <code>TRUE</code> when Output 1 '''Load''' is '''between 200 and 300 Watts for 5s'''.
Podmínka se vyhodnotí jako **true** v případě, že se hodnota proudu bude nacházet mezi 100 a 200 mA po dobu 5s.
+
 
```
+
<nowiki>
 
{
 
{
 
   "type": "RANGE",
 
   "type": "RANGE",
 
   "source": "OUTPUTS/1/CURRENT",
 
   "source": "OUTPUTS/1/CURRENT",
   "lowerBound": 100,
+
   "lowerBound": 200,
   "upperBound": 200,
+
   "upperBound": 300,
 
   "timeHysteresis": 5
 
   "timeHysteresis": 5
 +
}</nowiki>
  
}
+
= ZONES =
``` 
+
Opposed from a previous type, ZONE-type PAB detects, whether a monitored variable finds itself in a specified zone. State of PAB indicates what zone number (index) is the measured variable currently in. Zones are defined by their <code>thresholds</code> (lower bounds) and there must be at least one threshold specified.
 +
Monitored value must be present in a defined interval for period of time defined in <code>timeHysteresis</code>.
  
Podmínka se vyhodnotí dle stanovených zón v případě, že se hodnota proudu bude nacházet v jedné ze zón po dobu 10s.
+
== Structure ==
Př.: Pokud bude proud 130mA po dobu alespoň 10s, vyhodnotí se podmínka jako 2 (číslo zóny).
+
{| class="wikitable"
```
+
|-
 +
! Variable
 +
! Value
 +
! Description
 +
|-
 +
| type
 +
| ZONE
 +
| PAB type
 +
|-
 +
| source
 +
| OUTPUTS/'''x'''/(LOAD/CURRENT/POWER)
 +
| The monitored variable. '''x''' indicates input / output number.
 +
|-
 +
| timeHysteresis
 +
| int
 +
| '''[s]''' Monitored value must be present in defined interval for amount of time defined here.
 +
 
 +
Eg: If the time hysteresis is equal to 5, monitored value must be within a defined interval for at least 5s. Only then it will be evaluated.
 +
|-
 +
| thresholds
 +
| list of integers
 +
| lower-bounds of individual zones intervals
 +
|}
 +
 
 +
== Examples ==
 +
 
 +
PAB is evaluated according to the specified zones when the Output 2 '''Current''' value is in one of the zones for 10s.
 +
Zone numbers are as following:
 +
* '''0''': 0 - 49 mA
 +
* '''1''': 50 - 99 mA
 +
* '''2''': 100 - 149 mA
 +
* '''3''': 150 - 199 mA
 +
* '''4''': 200+ mA
 +
 
 +
Eg: If the Current value is 130mA for at least 10s, PAB is evaluated as 2.
 +
 
 +
<nowiki>
 
{
 
{
 
   "type": "ZONES",
 
   "type": "ZONES",
Line 94: Line 124:
 
   ],
 
   ],
 
   "timeHysteresis": 10
 
   "timeHysteresis": 10
}
+
}</nowiki>
```
 
 
 
## Otázky / Připomínky
 
* Digital inputs - states?
 

Revision as of 11:01, 18 February 2022

The PAB (Power Analysis Block) is a function available for NETIO devices that periodically evaluates sets of conditions. Based on these conditions, subsequent Rules can be executed. These conditions can consist of one or more of following variables:

  • Current [mA]
  • Energy [Wh]
  • Load [W]
  • Power Factor
  • S0 pulses

Rules can then perform several actions described in section Rules. Every PAB is internally evaluated as having a discrete state which can be used as an input to a Rule mentioned above. State value is different for each type of PAB (described below). This state is also available in JSON protocol and therefore can be read externally.

There are two types of PABs available: RANGE & ZONES. Each type has different states and configuration options.


RANGE

True/False-based evaluation. Detects whether a monitored value lies in specified interval (range) for a period of time. PAB evaluates to TRUE or FALSE. Interval is specified by lower lowerBound and upper upperBound boundaries. PAB evaluates to TRUE if a variable defined in source lies within for a period of time defined in timeHysteresis.

Configuration Structure

Variable Value Description
type RANGE PAB type
source OUTPUTS/x/(LOAD/CURRENT/POWER) The monitored variable. x indicates input / output number.
timeHysteresis int [s] Monitored value must be present in defined interval for amount of time defined here.

Eg: If the time hysteresis is equal to 5, monitored value must be within a defined interval for at least 5s. Only then it will be evaluated.

lowerBound int lower bound of the monitored value
upperBound int upper bound of the monitored value

Examples

Immediate evaluation

PAB evaluates to TRUE immediately as Output 1 Current value appears between 100 and 200 mA

{
  "type": "RANGE",
  "source": "OUTPUTS/1/CURRENT",
  "lowerBound": 100,
  "upperBound": 200,
  "timeHysteresis": 0
}

Evaluation with delay

PAB evaluates to TRUE when Output 1 Load is between 200 and 300 Watts for 5s.

{
  "type": "RANGE",
  "source": "OUTPUTS/1/CURRENT",
  "lowerBound": 200,
  "upperBound": 300,
  "timeHysteresis": 5
}

ZONES

Opposed from a previous type, ZONE-type PAB detects, whether a monitored variable finds itself in a specified zone. State of PAB indicates what zone number (index) is the measured variable currently in. Zones are defined by their thresholds (lower bounds) and there must be at least one threshold specified. Monitored value must be present in a defined interval for period of time defined in timeHysteresis.

Structure

Variable Value Description
type ZONE PAB type
source OUTPUTS/x/(LOAD/CURRENT/POWER) The monitored variable. x indicates input / output number.
timeHysteresis int [s] Monitored value must be present in defined interval for amount of time defined here.

Eg: If the time hysteresis is equal to 5, monitored value must be within a defined interval for at least 5s. Only then it will be evaluated.

thresholds list of integers lower-bounds of individual zones intervals

Examples

PAB is evaluated according to the specified zones when the Output 2 Current value is in one of the zones for 10s. Zone numbers are as following:

  • 0: 0 - 49 mA
  • 1: 50 - 99 mA
  • 2: 100 - 149 mA
  • 3: 150 - 199 mA
  • 4: 200+ mA

Eg: If the Current value is 130mA for at least 10s, PAB is evaluated as 2.

{
  "type": "ZONES",
  "source": "OUTPUTS/2/CURRENT",
  "thresholds": [
    50,
    100,
    150,
    200
  ],
  "timeHysteresis": 10
}