Difference between revisions of "Rules Complete Examples"

From wiki.netio-products.com
Jump to navigation Jump to search
(WatchDog definition)
Line 326: Line 326:
 
   }
 
   }
 
}</nowiki>
 
}</nowiki>
 +
 +
== NRXX - Total load (8QS)==
 +
{
 +
  "type": "RANGE",
 +
  "source": "OUTPUTS/TOTAL/LOAD",
 +
  "lowerBound": 30,
 +
  "upperBound": 100,
 +
  "timeHysteresis": 3
 +
}

Revision as of 15:31, 26 November 2021

NR01 - WatchDog

The WatchDog functionality is used to monitor connectivity to specified IP address (or URL) by sending PING request to it.

The ping in this example is sent every 60s and waits 5s for the device to respond. If the ping fails, Watchdog returns false and restarts (ACTION: 2 = SHORT OFF) device connected to first output. After restart, it waits 120 seconds and starts monitoring again. If the device does not respond, WatchDog remains in ERROR state until next successful ping.

WatchDog definition

WatchDog name: NR01_WDT

{
  "target": "192.168.101.180",
  "pingInterval": 60,
  "timeout": 5,
  "maxTimeouts": 0,
  "timeToReboot": 120,
  "maxRestarts": 0
}

Rule definition

Rule name: NR01_RULE

{
  "conditions": {
    "WDT/NR01_WDT/FAIL": true
  },
  "actions": {
    "OUTPUTS/1/ACTION": 2
  }
}

NR02 - Digital Inputs

Rule is used for managing outputs in response to change of Digital Inputs (DI) state. Rule monitors state of first DI. When DI switches from OFF (0) to ON (1), Rule switches (toggles) Outputs 1 & 2 to their opposite states (ACTION 4 = TOGGLE).

Rule definition

Rule name: NR02_RULE

{
  "conditions": {
    "INPUTS/1/STATE": "on"
  },
  "actions": {
    "OUTPUTS/1/ACTION": 4,
    "OUTPUTS/2/ACTION": 4
  }
}

NR03 - Load Watchdog

Rule monitors load (Watts) on Output 1. If the load is between 1-20W for at least 2 minutes, it restarts (ACTION 2 = SHORT OFF) the output. Example uses PAB (Power Analysis Block) functionality to determine if measured value (load in our case) lies in given range for a period of time. When it does, defined Rule triggers device restart.

PAB definition

PAB name: NR03_PAB

{
  "type": "RANGE",
  "source": "OUTPUTS/1/LOAD",
  "lowerBound": 1,
  "upperBound": 20,
  "timeHysteresis": 120
}

Rule definition

Rule name: NR03_RULE

{
  "conditions": {
    "PAB/NR03_PAB/IN": true
  },
  "actions": {
    "OUTPUTS/1/ACTION": 2
  }
}

NR04 - Load Watchdog with alarm to Cloud

Rule monitors load (Watts) on Output 1. If the load is between 1-20W for at least 30 minutes, it restarts (ACTION 2 = SHORT OFF) the output. In addition, it triggers an alarm in NETIO Cloud, which sends a notification to specified email address. This example needs a NETIO Cloud account with Premium version active for first output. There also has to be email notification enabled for the output.

Example uses PAB (Power Analysis Block) functionality to determine if measured value (load in our case) lies in given range for a period of time. When it does, defined Rule triggers device restart and sends alarm to Cloud.

PAB definition

PAB name: NR04_PAB

{
  "type": "RANGE",
  "source": "OUTPUTS/1/LOAD",
  "lowerBound": 1,
  "upperBound": 20,
  "timeHysteresis": 1800
}


Rule definition

Rule name: NR04_RULE

{
  "conditions": {
    "PAB/NR04_PAB/IN": true
  }
  "actions": {
    "OUTPUTS/1/ACTION": 2,
    "CLOUD/OUTPUT/1/ALARM": "${COND_RESULT}"
  }
}

NR05 - Load Watchdog with zones

Rule monitors load (Watts) on Output 1. Measured load is then classified to several zones defined with thresholds (limit values). Depending on the zone in which the measured load is currently located, different actions can be triggered. Load value has to be between defined threshold for at least 10seconds in order to be placed to respective zone. Example is composed of one PAB that classifies the zones and three Rules for 3 separate actions. Actions do the following:

  • Output 1 load lower than 1W: Output 2 = ON
  • Output 1 load between 1-20W: Output 3 = ON
  • Output 1 load between 20-200W: Output 4 = ON

PAB definition

PAB name: NR05_PAB

{
  "type": "ZONES",
  "source": "OUTPUTS/2/CURRENT",
  "thresholds": [
    1,
    20,
    200
  ],
  "timeHysteresis": 10
}

Rules definitions

Rule 1 name: NR05_RULE_1

{
  "conditions": {
    "PAB/NR05_PAB/ZONE": 0
  },
  "actions": {
    "OUTPUTS/2/ACTION": 1,
    "OUTPUTS/3/ACTION": 0,
    "OUTPUTS/4/ACTION": 0,
  }
}

Rule 2 name: NR05_RULE_2

{
  "conditions": {
    "PAB/NR05_PAB/ZONE": 0
  },
  "actions": {
    "OUTPUTS/2/ACTION": 0,
    "OUTPUTS/3/ACTION": 1,
    "OUTPUTS/4/ACTION": 0,
  }
}

Rule 3 name: NR05_RULE_3

{
  "conditions": {
    "PAB/NR05_PAB/ZONE": 0
  },
  "actions": {
    "OUTPUTS/2/ACTION": 0,
    "OUTPUTS/3/ACTION": 0,
    "OUTPUTS/4/ACTION": 1,
  }
}

NR06 - WatchDog for 2 IPs

The WatchDog functionality is used to monitor connectivity to specified IP address (or URL) by sending PING request to it.

In this example, we monitor two IPs and we want to restart device connected to Output 1 if none of the addresses reply. The ping for both IPs is sent every 30s and waits 5s for device to respond. There are 5 consecutive timeouts tolerated before the ping is considered as failed. When the ping fails, Watchdog returns false and remains in ERROR state.

In case both of the defined WatchDogs are in ERORR state, the Rule is triggered which then restarts Output 1.

WatchDogs definition

WatchDog name: NR06_WDT_1

{
  "target": "192.168.1.51",
  "pingInterval": 30,
  "timeout": 5,
  "maxTimeouts": 5
}

WatchDog name: NR06_WDT_2

{
  "target": "192.168.1.52",
  "pingInterval": 60,
  "timeout": 5,
  "maxTimeouts": 5
}

Rule definition

Rule name: NR06_RULE

{
  "conditions": {
    "operator": "AND"
    "WDT/NR06_WDT_1/FAIL": true
    "WDT/NR06_WDT_2/FAIL": true
  },
  "actions": {
    "OUTPUTS/1/ACTION": 2
  }
}

NR07 - Synchronized outputs states during working hours

Rule keeps track of first output state and when it changes, it switches output 2 to the same state. However, we want this synchronization only to work during working hours. We define the time with Schedule functionality and use it as a filter (mask) in Rules. Schedule can be defined manually or imported as a configuration file.

Schedule definition

Schedule name: NR07_SCHEDULE

NR070 Schedule

Rule definition

Rule name: NR07_RULE

{
  "conditions": {
    "OUTPUTS/1/STATE": "on"
  },
  "filters": {
    "SCHEDULE/NR07_SCHEDULE/ACTIVE": true
  },
  "actions": {
    "OUTPUTS/2/ACTION": "${COND_RESULT}"
  }
}

NR08 - Load Watchdog -> Turn output ON after period of time

In this example we want to measure load on output 1 and indicate when the power is abnormally low for a period of time by switching device on Output 2 ON (could be control light, sound alarm etc.).

In PAB we define indication for low power usage (1-20W) that is measured for period of 30 minutes (1800 seconds). In Rule we define switching Output 2 = ON (ACTION 1 = TURN ON) based on fulfilled PAB condition. This set up counts with human interaction after the Rule action gets processed. (e.g. restarting/replacing device on Output 1 and turning Output 2 OFF). It is possible to alter this behavior in such a way that the control light (Output 2) turns automatically OFF when load on Output 1 returns to standard values, i.e. higher than 20W (device gets repaired/replaced) or drops to 0W (device was removed or Output 1 turned OFF). This setup is defined in Rule NR08_ALT

PAB definition

PAB name: NR08_PAB

{
  "type": "RANGE",
  "source": "OUTPUTS/1/LOAD",
  "lowerBound": 1,
  "upperBound": 20,
  "timeHysteresis": 1800
}

Rule definition

Rule name: NR08_RULE

{
  "conditions": {
    "PAB/NR08_PAB/IN": true
  },
  "actions": {
    "OUTPUTS/2/ACTION": 1
  }
}

Rule name: NR08_RULE_ALT

{
  "conditions": {
    "PAB/NR08_PAB/IN": true
  },
  "actions": {
    "OUTPUTS/2/ACTION": "${COND_RESULT}"
  }
}

NR09 - Digital Inputs with Schedule

Examples shows usage when we want to detect switching of Digital Input to ON state (1) but to (not) react only during specified hours (e.g. outside of working hours). Reaction hours are defined with Schedule functionality. Schedule can be defined manually or imported as a configuration file.

Schedule definition

Schedule name: NR09_SCHEDULE

Rule definition

Rule name: NR09_RULE

{
  "conditions": {
    "INPUTS/1/STATE": "on"
  },
  "filters": {
    "SCHEDULE/NR09_SCHEDULE/ACTIVE": false
  },
  "actions": {
    "OUTPUTS/1/ACTION": 2
  }
}

NRXX - Total load (8QS)

{

 "type": "RANGE",
 "source": "OUTPUTS/TOTAL/LOAD",
 "lowerBound": 30,
 "upperBound": 100,
 "timeHysteresis": 3

}