The PAB (Power Analyzing Block) define sets of conditions for measured variables (current, voltage, S0 pulses etc.). Various rules can be set based on these conditions. Rules can perform actions such as sending alarm to the Cloud service, restarting outputs, etc.
+
The PAB (Power Analyzing Block) define sets of conditions for measured variables (current [mA], voltage, S0 pulses etc.). Based on each PAB state one or several RULEs can be executed. Each one Rule can perform several actions (Set Output, Short Off (restart) output, Toggle output or send Alarm state to the NETIO Cloud service. Based on this Alarm state can NETIO Cloud send email to defined recipient.
The PAB condition output is also available for use in selected protocols.
+
All PABs are listed in the JSON protocol wit their current states. It can be used by 3rd party software.  
  
 
== Types ==
 
== Types ==
 
There are two types of PAB available:
 
There are two types of PAB available:
  
# '''RANGE''' - Evaluation YES/NO (TRUE/FALSE)
+
# '''RANGE''' - Function state = YES/NO (TRUE/FALSE) - For example: O1 current <200 mA - 1000 mA>.
# '''ZONE''' - Evaluation using specified intervals
+
# '''ZONE''' - Function state = one of predefined value intervals - For example: O1 current = 1 (0 = <0-100mA>, 1 = <100-500mA>, 2 = <501-16000mA>)
  
Each type uses specific variables and is described in detail below. 
 
  
 
PABs can work with the specified quantities:
 
PABs can work with the specified quantities:

Revision as of 16:52, 16 November 2021

The PAB (Power Analyzing Block) define sets of conditions for measured variables (current [mA], voltage, S0 pulses etc.). Based on each PAB state one or several RULEs can be executed. Each one Rule can perform several actions (Set Output, Short Off (restart) output, Toggle output or send Alarm state to the NETIO Cloud service. Based on this Alarm state can NETIO Cloud send email to defined recipient. All PABs are listed in the JSON protocol wit their current states. It can be used by 3rd party software.

Types

There are two types of PAB available:

  1. RANGE - Function state = YES/NO (TRUE/FALSE) - For example: O1 current <200 mA - 1000 mA>.
  2. ZONE - Function state = one of predefined value intervals - For example: O1 current = 1 (0 = <0-100mA>, 1 = <100-500mA>, 2 = <501-16000mA>)


PABs can work with the specified quantities:

  • Current: OUTPUTS/1/CURRENT [mA]
  • Load: OUTPUTS/2/LOAD [W]
  • Energy: OUTPUTS/4/POWER [Wh]
  • Output No. 8 state: OUTPUTS/8/STATE [int 0/1]

General structure for defining a variable is: <INPUT/OUTPUT>/ID/<monitored variable>