== Example for PAB - RANGE == | == Example for PAB - RANGE == | ||
The setting described below is intended to monitor a device connected to first output. The device is expected to have a certain load between 100W and 500W during working hours. If the consumption is too low or too high (i.e. outside the specified interval) for more than 10s, it is likely that the device works incorrectly and restart is needed to correct its state. | The setting described below is intended to monitor a device connected to first output. The device is expected to have a certain load between 100W and 500W during working hours. If the consumption is too low or too high (i.e. outside the specified interval) for more than 10s, it is likely that the device works incorrectly and restart is needed to correct its state. | ||
Line 31: | Line 30: | ||
"actions": { | "actions": { | ||
"OUTPUTS/1/ACTION": 2 | "OUTPUTS/1/ACTION": 2 | ||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
} | } | ||
}</nowiki> | }</nowiki> | ||
Line 129: | Line 110: | ||
} | } | ||
} </nowiki> | } </nowiki> | ||
+ | |||
+ | == Watchdog example == | ||
+ | |||
+ | The Watchdog monitors specified IP address. The ping is sent every 60s and waits 5s for the device to respond. If the ping fails twice in a row, Watchdog returns <code>false</code> and restarts the device. After restart, it waits 120 seconds and starts monitoring again. This cycle repeats a total of 3 times, and if the device does not respond even once, the Watchdog remains in ERROR state. | ||
+ | |||
+ | ===Watchdog definition=== | ||
+ | |||
+ | Watchdog name: '''Watch_101_180''' | ||
+ | |||
+ | <nowiki> | ||
+ | { | ||
+ | "target": "192.168.101.180", | ||
+ | "pingInterval": 60, | ||
+ | "timeout": 5, | ||
+ | "maxTimeouts": 2, | ||
+ | "timeToReboot": 120, | ||
+ | "maxRestarts": 3 | ||
+ | }</nowiki> | ||
+ | |||
+ | |||
+ | ===Rule definition=== | ||
+ | |||
+ | Rule name: '''Watch_101_180_restart''' | ||
+ | |||
+ | <nowiki> | ||
+ | { | ||
+ | "conditions": { | ||
+ | "WDT/Watch_101_180/FAIL": true | ||
+ | }, | ||
+ | "actions": { | ||
+ | "OUTPUTS/1/ACTION": 2 | ||
+ | } | ||
+ | }</nowiki> | ||
+ | |||
+ | == Example for Digital Inputs == | ||
+ | |||
+ | Rule monitors state of digital input (DI) No. 1. When DI switches to ON (1), it sends alarm to Cloud for Output 1. When DI switches back to OFF, the alarm turns off as well. | ||
+ | |||
+ | ===Rule definition=== | ||
+ | |||
+ | Rule name: '''RULE_DI''' | ||
+ | |||
+ | <nowiki> | ||
+ | { | ||
+ | "conditions": { | ||
+ | "INPUTS/1/STATE": "on" | ||
+ | }, | ||
+ | "actions": { | ||
+ | "CLOUD/OUTPUT/1/ALARM": "${COND_RESULT}" | ||
+ | } | ||
+ | }</nowiki> | ||
== Example for devices without measurements == | == Example for devices without measurements == |
Revision as of 17:32, 22 November 2021
Contents
Example for PAB - RANGE
The setting described below is intended to monitor a device connected to first output. The device is expected to have a certain load between 100W and 500W during working hours. If the consumption is too low or too high (i.e. outside the specified interval) for more than 10s, it is likely that the device works incorrectly and restart is needed to correct its state.
PAB definition
PAB name: Watch_out1_load
{ "type": "RANGE", "source": "OUTPUTS/1/LOAD", "lowerBound": 100, "upperBound": 500, "timeHysteresis": 10 }
Rules definition
Note: We use the Schedules functionality in the filter to define working hours of the week. The device monitoring will only work at time set in the Schedule.
Schedule name: Working_hours
{ "conditions": { "PAB/Watch_out1_load/IN": 0 }, "filters": { "SCHEDULE/Working_hours/ACTIVE": true }, "actions": { "OUTPUTS/1/ACTION": 2 } }
Example for PAB - RANGE (multiple actions for one condition)
Defined condition checks a device connected to output 4. The device is expected to have a maximum load of 600W. If the load is too high, we want to immediately turn off the device and send an alarm to Cloud.
PAB definition
PAB name: Watch_out4_load
{ "type": "RANGE", "source": "OUTPUTS/4/LOAD", "lowerBound": 0, "upperBound": 600 }
Action definition
{ "conditions": { "PAB/Watch_out4_load/IN": 0 } "actions": { "OUTPUTS/4/ACTION": 0, "CLOUD/OUTPUT/1/ALARM": "${COND_RESULT}" } }
Example for PAB - ZONES
In this condition, the value of current at the output 2 is monitored. It is then classified to respective zone according to measured value. Depending on the zone in which is classified, different actions can be triggered:
- If the value of current is in zone 0, restart device on output 1
- If the value of current is in zone 2, turn ON alarm in Cloud
PAB definition
PAB name: Watch_out2_current
{ "type": "ZONES", "source": "OUTPUTS/2/CURRENT", "thresholds": [ 50, 150, ], "timeHysteresis": 10 }
Rules definition
Must be defined in two separate Rules because they contain different conditions:
- Rule name: Zone_restart
- Description: If the PAB is in zone 0 (0-49mA), restart the device at output 1
{ "conditions": { "PAB/Watch_out2_current/ZONE": 0 }, "actions": { "OUTPUTS/1/ACTION": 2 } }
- Rule name: Zone_alarm
- Description: If the PAB is in zone 2 (150+ mA), send alarm to Cloud
{ "conditions": { "PAB/Watch_out2_current/ZONE": 2 }, "actions": { "CLOUD/OUTPUT/1/ALARM": "${COND_RESULT}" } }
Watchdog example
The Watchdog monitors specified IP address. The ping is sent every 60s and waits 5s for the device to respond. If the ping fails twice in a row, Watchdog returns false
and restarts the device. After restart, it waits 120 seconds and starts monitoring again. This cycle repeats a total of 3 times, and if the device does not respond even once, the Watchdog remains in ERROR state.
Watchdog definition
Watchdog name: Watch_101_180
{ "target": "192.168.101.180", "pingInterval": 60, "timeout": 5, "maxTimeouts": 2, "timeToReboot": 120, "maxRestarts": 3 }
Rule definition
Rule name: Watch_101_180_restart
{ "conditions": { "WDT/Watch_101_180/FAIL": true }, "actions": { "OUTPUTS/1/ACTION": 2 } }
Example for Digital Inputs
Rule monitors state of digital input (DI) No. 1. When DI switches to ON (1), it sends alarm to Cloud for Output 1. When DI switches back to OFF, the alarm turns off as well.
Rule definition
Rule name: RULE_DI
{ "conditions": { "INPUTS/1/STATE": "on" }, "actions": { "CLOUD/OUTPUT/1/ALARM": "${COND_RESULT}" } }
Example for devices without measurements
Defined rule keeps output 1 state the same as output 3
Rule definition
Rule name: RULE_OUT
{ "conditions": { "OUTPUTS/3/STATE": "on" }, "actions": { "OUTPUTS/1/ACTION": "${COND_RESULT}" } }