The PAB (Power Analyzing Block) define sets of conditions for measured variables (current, voltage, S0 pulses etc.). Various rules can be set based on these conditions. Rules can perform actions such as sending alarm to the Cloud service, restarting outputs, etc.
+
The PAB (Power Analysis Block) is set of Condition & Rules (CR). It's set of most common functions available for NETIO devices. Based on each '''Condition''', subsequent [https://wiki.netio-products.com/index.php?title=Rules '''Rules'''] can be executed.
The PAB condition output is also available for use in selected protocols.
+
User friendly examples are prepared as [https://wiki.netio-products.com/index.php?title=Rules_Complete_Examples '''CRxx Conditions & Rules - examples''']
  
There are two types of PAB available:
 
1) RANGE - Evaluation YES/NO (true/false) 
 
2) ZONE - Evaluation using specified intervals 
 
Each type uses specific variables and is described in detail below. 
 
  
PABs can work with the specified quantities:
+
The '''Rules''' can be triggered based on a '''Condition''' - analysis of the state of one or more variables:
  * Current: OUTPUTS/1/CURRENT **[mA]**
+
* Current [mA]
  * Load: OUTPUTS/8/LOAD **[W]**
+
* Energy [Wh]
  * Energy: OUTPUTS/4/POWER **[Wh]**
+
* Load [W]
  * Output no. 1 state: OUTPUTS/1/STATE **[int 0/1]**
+
* Power Factor
General structure for defining a variable is: `<INPUT/OUTPUT>/ID/<monitored variable>`
+
* S0 pulses
 +
* TEMP [°C], [°F] - available from FW 5.0.3+
  
## PAB - RANGE 
+
Rules can then perform several actions described in section [https://wiki.netio-products.com/index.php?title=Rules '''Rules'''].
True/False-based evaluation. If the monitored value is in specified interval for a time period defined in `timeHysteresis`, PAB evaluates as `True`. Otherwise it evaluates as `False`.
+
Every PAB is internally evaluated as having a discrete state which can be used as an input to a Rule mentioned above. State value is different for each type of PAB (described below). This state is also available in JSON protocol and therefore can be read externally.
  
### Structure
+
There are two types of PABs available: '''RANGE''' & '''ZONES'''. Each type has different states and configuration options.
 +
 
 +
 
 +
= RANGE =
 +
True/False-based evaluation. Detects whether a monitored value lies in specified interval (range) for a period of time. PAB evaluates to <code>TRUE</code> or <code>FALSE</code>.
 +
Interval is specified by lower <code>lowerBound</code> and upper <code>upperBound</code> boundaries. PAB evaluates to <code>TRUE</code> if a variable defined in <code>source</code> lies within for a period of time defined in <code>timeHysteresis</code>.
 +
 
 +
== Configuration Structure ==
 
{| class="wikitable"
 
{| class="wikitable"
 
|-
 
|-
Line 29: Line 33:
 
|-
 
|-
 
| source  
 
| source  
| OUTPUTS/**x**/(LOAD/CURRENT/POWER) <br> INPUTS/**x**/STATE
+
| OUTPUTS/'''x'''/(LOAD/CURRENT/POWER/TEMP)
| The monitored variable. **x** indicates input / output number.
+
| The monitored variable. '''x''' indicates input / output number.
 
|-
 
|-
 
| timeHysteresis  
 
| timeHysteresis  
 
| int  
 
| int  
| [s] Monitored value must be present in defined interval for amount of time defined here. Eg: If the time hysteresis is equal to 5, monitored value must be within a defined interval for at least 5s. Only then it will be evaluated.
+
| [s] Monitored value must be present in defined interval for amount of time defined here.
 +
 
 +
Eg: If the time hysteresis is equal to 5, monitored value must be within a defined interval for at least 5s. Only then it will be evaluated.
 
|-
 
|-
 
| lowerBound  
 
| lowerBound  
Line 45: Line 51:
 
|}
 
|}
  
## PAB - ZONE 
+
== Examples ==
Zone-based evaluation. 1 or more zones can be set. Zones are divided using the values specified in the `thresholds` variable.
 
Monitored value must be present in defined interval for amount of time defined here. The PAB condition is evaluated as a number (integer) equal to the interval order. Eg. At two specified intervals, the PAB value can be 0, 1, or 2.
 
  
### Struktura 
+
=== Immediate evaluation ===
| Proměnná | Hodnoty | Popis |
+
PAB evaluates to <code>TRUE</code> immediately as Output 1 '''Current''' value appears '''between 100 and 200 mA'''
| ------ | ------ | ------ |
+
<nowiki>
| type | ZONE | typ PAB |
 
| source | OUTPUTS/**x**/(LOAD/CURRENT/POWER) <br> INPUTS/**x**/STATE |  Měřená hodnota, kterou sledujeme. **x** udává číslo vstupu/výstupu.|
 
| timeHysteresis | int | [s] Časový interval, ve kterém se musí nacházet sledovaná hodnota. Př.: Pokud je hystereze rovná 5, musí se sledovaná hodnota nacházet v definovaném intervalu (intervalech) alespoň 5s. Až následně dojde k jejímu vyhodnoceí. |
 
| thresholds | list[int] |  seznam spodních hranic intervalů pro přechod mezi zónami
 
 
 
## Příklady
 
Podmínka se vyhodnotí jako **true** okamžítě, jakmile se hodnota proudu objeví mezi 100 a 200 mA.
 
```
 
 
{
 
{
 
   "type": "RANGE",
 
   "type": "RANGE",
Line 66: Line 62:
 
   "upperBound": 200,
 
   "upperBound": 200,
 
   "timeHysteresis": 0
 
   "timeHysteresis": 0
 +
}</nowiki>
  
}
+
=== Evaluation with delay ===
``` 
+
PAB evaluates to <code>TRUE</code> when Output 1 '''Load''' is '''between 200 and 300 Watts for 5s'''.
Podmínka se vyhodnotí jako **true** v případě, že se hodnota proudu bude nacházet mezi 100 a 200 mA po dobu 5s.
+
 
```
+
<nowiki>
 
{
 
{
 
   "type": "RANGE",
 
   "type": "RANGE",
 
   "source": "OUTPUTS/1/CURRENT",
 
   "source": "OUTPUTS/1/CURRENT",
   "lowerBound": 100,
+
   "lowerBound": 200,
   "upperBound": 200,
+
   "upperBound": 300,
 
   "timeHysteresis": 5
 
   "timeHysteresis": 5
 +
}</nowiki>
 +
 +
= ZONES =
 +
Opposed from a previous type, ZONE-type PAB detects, whether a monitored variable finds itself in a specified zone. State of PAB indicates what zone number (index) is the measured variable currently in. Zones are defined by their <code>thresholds</code> (lower bounds) and there must be at least one threshold specified.
 +
Monitored value must be present in a defined interval for period of time defined in <code>timeHysteresis</code>.
 +
 +
== Structure ==
 +
{| class="wikitable"
 +
|-
 +
! Variable
 +
! Value
 +
! Description
 +
|-
 +
| type
 +
| ZONES
 +
| PAB type
 +
|-
 +
| source
 +
| OUTPUTS/'''x'''/(LOAD/CURRENT/POWER/TEMP)
 +
| The monitored variable. '''x''' indicates input / output number.
 +
|-
 +
| timeHysteresis
 +
| int
 +
| '''[s]''' Monitored value must be present in defined interval for amount of time defined here.
 +
 +
Eg: If the time hysteresis is equal to 5, monitored value must be within a defined interval for at least 5s. Only then it will be evaluated.
 +
|-
 +
| thresholds
 +
| list of integers
 +
| lower-bounds of individual zones intervals
 +
|}
 +
 +
== Examples ==
 +
 +
PAB is evaluated according to the specified zones when the Output 2 '''Current''' value is in one of the zones for 10s.
 +
Zone numbers are as following:
 +
* '''0''': 0 - 49 mA
 +
* '''1''': 50 - 99 mA
 +
* '''2''': 100 - 149 mA
 +
* '''3''': 150 - 199 mA
 +
* '''4''': 200+ mA
  
}
+
Eg: If the Current value is 130mA for at least 10s, PAB is evaluated as 2.
``` 
 
  
Podmínka se vyhodnotí dle stanovených zón v případě, že se hodnota proudu bude nacházet v jedné ze zón po dobu 10s.  
+
  <nowiki>
Př.: Pokud bude proud 130mA po dobu alespoň 10s, vyhodnotí se podmínka jako 2 (číslo zóny).
 
```
 
 
{
 
{
 
   "type": "ZONES",
 
   "type": "ZONES",
Line 94: Line 129:
 
   ],
 
   ],
 
   "timeHysteresis": 10
 
   "timeHysteresis": 10
 +
}</nowiki>
 +
 +
= DAYLIGHT (sunrise / sunset) <sup><code>FW 4.0.0+</code></sup> =
 +
Enables launching actions based on sunrise / sunset of current place.
 +
 +
== Structure ==
 +
{| class="wikitable"
 +
|-
 +
! Variable
 +
! Value
 +
! Description
 +
|-
 +
| type
 +
| DAYLIGHT
 +
| PAB type
 +
|-
 +
| longitude
 +
| str "14.4129433E" OR int -73.8390597
 +
| East/West coordinates
 +
|-
 +
| latitude
 +
| str "50.0058144N" OR int -16.5237353
 +
| North/South coordinates
 +
|-
 +
| altitude
 +
| Number of meters above sea level
 +
| 8848
 +
|-
 +
| sunriseDelay
 +
| int [min]
 +
| Delay of PAB activation/deactivation to sunrise
 +
|-
 +
| sunsetDelay
 +
| int [min]
 +
| Delay of PAB activation/deactivation to sunset
 +
|}
 +
 +
== Examples ==
 +
 +
=== PAB ===
 +
 +
<nowiki>
 +
{
 +
  "type": "DAYLIGHT",
 +
  "longitude": "14.4129433E",
 +
  "latitude": "50.0058144N",
 +
  "altitude": 247,
 +
  "sunriseDelay": 240,
 +
  "sunsetDelay": -180
 
}
 
}
```
+
</nowiki>
 +
 
 +
or
  
## Otázky / Připomínky
+
<nowiki>
* Digital inputs - states?
+
{
 +
  "type": "DAYLIGHT",
 +
  "longitude": -16.5237353,
 +
  "latitude": 28.4162475,
 +
  "altitude": 247,
 +
  "sunriseDelay": 240,
 +
  "sunsetDelay": -180
 +
}
 +
</nowiki>

Latest revision as of 09:42, 29 July 2024

The PAB (Power Analysis Block) is set of Condition & Rules (CR). It's set of most common functions available for NETIO devices. Based on each Condition, subsequent Rules can be executed. User friendly examples are prepared as CRxx Conditions & Rules - examples


The Rules can be triggered based on a Condition - analysis of the state of one or more variables:

  • Current [mA]
  • Energy [Wh]
  • Load [W]
  • Power Factor
  • S0 pulses
  • TEMP [°C], [°F] - available from FW 5.0.3+

Rules can then perform several actions described in section Rules. Every PAB is internally evaluated as having a discrete state which can be used as an input to a Rule mentioned above. State value is different for each type of PAB (described below). This state is also available in JSON protocol and therefore can be read externally.

There are two types of PABs available: RANGE & ZONES. Each type has different states and configuration options.


RANGE

True/False-based evaluation. Detects whether a monitored value lies in specified interval (range) for a period of time. PAB evaluates to TRUE or FALSE. Interval is specified by lower lowerBound and upper upperBound boundaries. PAB evaluates to TRUE if a variable defined in source lies within for a period of time defined in timeHysteresis.

Configuration Structure

Variable Value Description
type RANGE PAB type
source OUTPUTS/x/(LOAD/CURRENT/POWER/TEMP) The monitored variable. x indicates input / output number.
timeHysteresis int [s] Monitored value must be present in defined interval for amount of time defined here.

Eg: If the time hysteresis is equal to 5, monitored value must be within a defined interval for at least 5s. Only then it will be evaluated.

lowerBound int lower bound of the monitored value
upperBound int upper bound of the monitored value

Examples

Immediate evaluation

PAB evaluates to TRUE immediately as Output 1 Current value appears between 100 and 200 mA

{
  "type": "RANGE",
  "source": "OUTPUTS/1/CURRENT",
  "lowerBound": 100,
  "upperBound": 200,
  "timeHysteresis": 0
}

Evaluation with delay

PAB evaluates to TRUE when Output 1 Load is between 200 and 300 Watts for 5s.

{
  "type": "RANGE",
  "source": "OUTPUTS/1/CURRENT",
  "lowerBound": 200,
  "upperBound": 300,
  "timeHysteresis": 5
}

ZONES

Opposed from a previous type, ZONE-type PAB detects, whether a monitored variable finds itself in a specified zone. State of PAB indicates what zone number (index) is the measured variable currently in. Zones are defined by their thresholds (lower bounds) and there must be at least one threshold specified. Monitored value must be present in a defined interval for period of time defined in timeHysteresis.

Structure

Variable Value Description
type ZONES PAB type
source OUTPUTS/x/(LOAD/CURRENT/POWER/TEMP) The monitored variable. x indicates input / output number.
timeHysteresis int [s] Monitored value must be present in defined interval for amount of time defined here.

Eg: If the time hysteresis is equal to 5, monitored value must be within a defined interval for at least 5s. Only then it will be evaluated.

thresholds list of integers lower-bounds of individual zones intervals

Examples

PAB is evaluated according to the specified zones when the Output 2 Current value is in one of the zones for 10s. Zone numbers are as following:

  • 0: 0 - 49 mA
  • 1: 50 - 99 mA
  • 2: 100 - 149 mA
  • 3: 150 - 199 mA
  • 4: 200+ mA

Eg: If the Current value is 130mA for at least 10s, PAB is evaluated as 2.

{
  "type": "ZONES",
  "source": "OUTPUTS/2/CURRENT",
  "thresholds": [
    50,
    100,
    150,
    200
  ],
  "timeHysteresis": 10
}

DAYLIGHT (sunrise / sunset) FW 4.0.0+

Enables launching actions based on sunrise / sunset of current place.

Structure

Variable Value Description
type DAYLIGHT PAB type
longitude str "14.4129433E" OR int -73.8390597 East/West coordinates
latitude str "50.0058144N" OR int -16.5237353 North/South coordinates
altitude Number of meters above sea level 8848
sunriseDelay int [min] Delay of PAB activation/deactivation to sunrise
sunsetDelay int [min] Delay of PAB activation/deactivation to sunset

Examples

PAB

{
  "type": "DAYLIGHT",
  "longitude": "14.4129433E",
  "latitude": "50.0058144N",
  "altitude": 247,
  "sunriseDelay": 240,
  "sunsetDelay": -180
}

or

{
  "type": "DAYLIGHT",
  "longitude": -16.5237353,
  "latitude": 28.4162475,
  "altitude": 247,
  "sunriseDelay": 240,
  "sunsetDelay": -180
}